General Information |
STYLE: |
Insertion Mass Flow Meter |
SENSOR: |
Two reference-grade platinum RTD clad in 316SS sheath |
MATERIAL: |
Wetted metal components: 316SS |
POWER: |
24VDC Standard (12VDC or 115/230VAC optional) |
POWER DISSIPATION: |
< 2.5 w |
ELECTRONICS: |
Microprocessor-based (Hybrid-Digital) |
ELECTRONICS ENCLOSURE: |
Integral mount, NEMA 4 enclosure |
DISPLAY: |
High contrast photo-emissive OLED graphical display (Flow rate, Totalizer, Temperature) |
TURNDOWN: |
100 to 1 |
RESOLUTION: |
1000 to 1 |
LOW-END SENSITIVITY: |
5 SFPM |
FIELD CALIBRATION CHECK: |
Yes – Digital system allows raw signal validation (milli-watts) |
COMMUNICATIONS: |
Modbus® compliant RS485 RTU or optional HART® communications |
APPROVALS: |
Class I, Div, 2 Groups B, C, D T4. (24 VDC). ANSI/ISA 12.12.01, CSA 2202; ATEXnA – Div 2 (24 VDC) |
FIELD RECONFIGURABLE: |
SageCom required |
FLOW ACCURACY: |
+/- 0.5% of Full Scale +/- 1% of reading (Enhanced accuracy optionally available with limited turn-down) |
FLOW REPEATABILITY: |
0.2% |
RESPONSE TIME: |
1 second time constant |
GAS TEMPERATURE RANGE: |
-40 ° TO 200 °F (93 °C) Standard (if higher temperature needed, contact Sage) |
GAS PRESSURE: |
500 PSIG (if higher pressure needed, contact Sage) |
FLOW OUTPUT: |
4 to 20 mA for Rate; 24VDC pulse for Totalized value |
TEMPERATURE OUTPUT: |
Through Modbus® only |
AMBIENT TEMPERATURE: |
-40 ° to 150 °F (65 °C) |
PROBE STYLE / LENGTH: |
1/2″ OD Probe (3/4″ optional) Lengths 6″ to 36″ |
RELAYS: |
N/A |
FLOW CONDITIONING: |
Captive Flow Conditioners available upon request with meter purchase |
ENCLOSURE DEPTH: |
DC: 4.35″ AC: 5.35″ |