| General Information | |
|---|---|
| STYLE: | Remote Insertion Mass Flow Meter |
| SENSOR: | Two reference-grade platinum RTD clad in 316SS sheath |
| MATERIAL: | Wetted metal components: 316SS |
| POWER: | 24VDC Standard (12VDC or 115/230VAC optional) |
| POWER DISSIPATION: | < 2.5 w |
| ELECTRONICS: | Microprocessor-based (Hybrid-Digital) |
| PROBE ENCLOSURE: | Junction Box is Explosion Proof, Class I, Div 2, Groups B, C, D (no electronics) |
| ELECTRONICS ENCLOSURE: | Integral mount, NEMA 4 enclosure |
| DISPLAY: | High contrast photo-emissive OLED graphical display (Flow rate, Totalizer, Temperature) |
| TURNDOWN: | 100 to 1 |
| RESOLUTION: | 1000 to 1 |
| LOW-END SENSITIVITY: | 5 SFPM |
| FIELD CALIBRATION CHECK: | Yes – Digital system allows raw signal validation (milli-watts) |
| COMMUNICATIONS: | Modbus® compliant RS485 RTU or optional HART® communications |
| APPROVALS: | Class I, Div, 2 Groups B, C, D T4. (24 VDC). ANSI/ISA 12.12.01, CSA 2202; ATEXnA – Div 2 (24 VDC) |
| FIELD RECONFIGURABLE: | SageCom required |
| FLOW ACCURACY: | +/- 0.5% of Full Scale +/- 1% of reading (Enhanced accuracy optionally available with limited turn-down) |
| FLOW REPEATABILITY: | 0.2% |
| RESPONSE TIME: | 1 second time constant |
| GAS TEMPERATURE RANGE: | Standard -40 ° to 200 °F (93 °C), Optional to 300 °F (149 °C) and 450 °F (232 °C) |
| GAS PRESSURE: | 500 PSIG (if higher pressure needed, contact Sage) |
| FLOW OUTPUT: | 4 to 20 mA for Rate |
| TOTALIZER: | 24VDC pulse for Totalized value |
| TEMPERATURE OUTPUT: | Through Modbus® only |
| AMBIENT TEMPERATURE: | -40 ° to 150 °F (66 °C) |
| PROBE STYLE / LENGTH: | 1/2″ OD Probe (3/4″ optional) Lengths 6″ to 36″ |
| RELAYS: | N/A |
| CABLE LENGTH: | 25′ Standard (max length 1000′) |
| FLOW CONDITIONING: | Captive Flow Conditioners available upon request with meter purchase |
| ENCLOSURE DEPTH: | DC: 4.35″ AC: 5.35″ |