General Information | |
---|
STYLE: | Remote Inline Mass Flow Meter |
SENSOR: | Two reference-grade platinum RTD clad in 316SS sheath |
MATERIAL: | Wetted metal components: 316SS |
POWER: | 24VDC Standard (12VDC or 115/230VAC optional) |
POWER DISSIPATION: | < 2.5 w |
ELECTRONICS: | Remote-Style Microprocessor-based (Hybrid-Digital) |
ELECTRONICS ENCLOSURE: | Junction Box is Explosion Proof, Class I, Div 2, Groups B, C, D (no electronics) |
TRANSMITTER ENCLOSURE: | Remote mount, NEMA 4 enclosure |
DISPLAY: | High contrast photo-emissive OLED graphical display (Flow rate, Totalizer, Temperature) |
TURNDOWN: | 100 to 1 |
RESOLUTION: | 1000 to 1 |
LOW-END SENSITIVITY: | 5 SFPM |
FIELD CALIBRATION CHECK: | Yes – Digital system allows raw signal validation (milli-watts) |
COMMUNICATIONS: | Modbus® compliant RS485 RTU or optional HART® communications |
APPROVALS: | Class I, Div, 2 Groups B, C, D T4. (24 VDC). ANSI/ISA 12.12.01, CSA 2202; ATEXnA – Div 2 (24 VDC) |
FIELD RECONFIGURABLE: | SageCom required |
FLOW ACCURACY: | +/- 0.5% of Full Scale +/- 1% of reading (Enhanced accuracy optionally available with limited turn-down) |
FLOW REPEATABILITY: | 0.2% |
RESPONSE TIME: | 1 second time constant |
GAS TEMPERATURE RANGE: | -Standard -40 ° TO 200 °F (93 °C) Optional to 300 °F (149 °C) and 450°F (232 °C) |
GAS PRESSURE: | 500 PSIG (if higher pressure needed, contact Sage) |
FLOW OUTPUT: | 4 to 20 mA for Rate |
TOTALIZER: | 24VDC pulse for Totalized value |
TEMPERATURE OUTPUT: | Through Modbus® only |
AMBIENT TEMPERATURE: | -40 ° TO 150 °F (66 °C) |
FLOW BODY: | 316SS Schedule 40 Flow Bodies sized from 1/4″ x 6″ long to 4″ x 12″ long. |
| Male NPT ends standard (Flanges and other options available) |
CABLE LENGTH: | 25′ Standard (max length 1000′) |
RELAYS: | N/A |
FLOW CONDITIONING: | Flow Conditioners are built into Inline Style Flow Bodies from 1/2″ to 4″ |
ENCLOSURE DEPTH: | DC: 4.35″ AC: 5.35″ |